E-katalogue
Fire resistant partition panels 102.02
Fire resistant partition panels are of the sandwich type, consisting of facing and internal filler. Mineral wool is used as the panel filler. Cable glands can be fitted in the panel for electrical connections.
DESCRIPTION
1 - Metal shield; 2 - Facing; 3 - Cable gland; 4 - Filler; 5 - Facing; 6 - Direction of use
Fire resistant panel EI15/EW30 |
Fire resistant panel EI15/EW30/EW45 |
1 - Filler; 2 - Facing; 3 - Profile "U"; 4 - Facing; 5 - Profile "BASIC" |
1 - Filler; 2 - Facing; 3 - 2x L profiles; 4 - Facing; 5 - 2x L profiles |
BENEFITS
- Quick assembly and disassembly allowing flexible change of the layout of the space
- Easy maintenance
- Color stability
- Corrosion protection
- Thermal and acoustic insulation
TECHNICAL DATA
Fire resistance |
---|
EI15 minutes for panel thickness 60 mm |
EI30 minutes for panel thickness 60 mm |
Panel thickness |
---|
60 mm |
Panel width W |
---|
1190 mm |
560 mm |
atypický mm |
W - width in mm according to dimensional range 560 mm, 1190 mm. It is possible to order atypical panel dimensions: min. dimension 300 mm, max. dimension 1190 mm. |
Panel height H |
---|
2550 mm |
3050 mm |
2750 mm |
atypický mm |
For EI15/EW30 Height according to standard dimensional range 2550, 2750, 3050 mm. Preferred dimensions 2550, 2750, 3050 mm. Min. dimension 300 mm, max. dimension 4000 mm. Panels of different width must be made as atypical (max. panel width is 1190 mm). |
Bottom end | |
---|---|
value | |
basic (tongue) | EI15/EW30 |
basic+reinforcement | EI15/EW30 |
clasic (straight) | EI15/EW30 - EI30/EW30 |
clasic+resistant reinforcement | EI15/EW30 |
clasic+reinforcement | EI15/EW30 |
groove | EI15/EW30 |
atypical |
Upper end | |
---|---|
value | |
basic (tongue) | EI15/EW30 |
basic+reinforcement | EI15/EW30 |
clasic (straight) | EI15/EW30 - EI30/EW30 |
clasic+reinforcement | EI15/EW30 |
groove | EI15/EW30 |
atypical | EI15/EW30 - EI30/EW30 |
Side reinforcement | |
---|---|
value | |
simple reinforcement | EI15/EW30 |
no side reinforcement | EI15/EW30 - EI30/EW30 |
reinforcement with fireproof linnng | EI30/EW30 |
left reinforcement, right reinforcement | EI30/EW30 |
reinforced reinforcement | EI30/EW30 |
The panel edge with the reinforcement is fitted with an expanding waterstop (foam tape). |
Number of cable glands | |
---|---|
value | |
no cable gland | EI15/EW30 - EI30/EW30 |
2 pcs (1 pc 85 mm from the left- 1 pc 85 mm from the right) | EI15/EW30 |
2 pcs (1 pc 250 mm from the left- 1 pc 250 mm from the right) | EI15/EW30 |
cable glands from the left, cable glands from the right | EI15/EW30 |
Example of designation in the case of multiple cable glands: Orientation and number of cable glands are specified. The first cable gland is 85 mm from the edge. Other cable glands are located 100 mm apart from each other as standard. 3;2 – Total of 5 pcs, 3 from the left side+2 from the right side.For atypical designs, it is necessary to specify A-atypical orientation, number. The dimension must be specified in the notes. |
Atypical design |
---|
Type design |
Atypical design |
Type design 0 - Unique specification out of offered versions Atypical design Q - atypical design that cannot be uniquely specified by a code |